Double Check Valve Testing in South Orange, NJ
Call us
(833) 990-5874
Certified testers
Reports filed with your utility
RPZ, DCVA and PVB
Price talked through by phone

Double Check Valve Testing in South Orange, NJ

A double check valve assembly, or DCVA, has two independent spring-loaded checks between two resilient-seated shutoffs and four test cocks. It is approved for low-hazard connections, so you see it on many fire lines, apartment services and some irrigation systems.

The tester bleeds and reads each check separately. Each one has to hold a differential of at least 1.0 psid. If a check reads lower, the cause is usually a worn rubber disc, a weak spring or debris across the seat.

Unlike an RPZ, a DCVA can be installed in a pit or vault in many jurisdictions, which brings its own problems. Flooded vaults make test cocks hard to reach and corrode the bolts. Testers often pump the vault before they can start.

Grizzly Backflow & Plumbing connects you with local testers in South Orange, NJ for double check valve testing, report filing with your purveyor and repair if a check fails. Good backflow prevention depends on both checks holding, not one. Call (833) 990-5874.

How it works

Four steps to backflow testing in South Orange, NJ

  1. 01

    Grab your notice

    Have the utility letter handy. It lists the device, serial number and due date.

  2. 02

    Talk it through

    Call (833) 990-5874. We go over the device type and the price before anything is booked.

  3. 03

    Test day

    A certified tester reads each check and the relief valve on a calibrated gauge.

  4. 04

    Report filed

    The report goes to your water utility, and you keep a copy for your records.

Coverage

Backflow Testing Services Across South Orange, NJ

Backflow testing for the neighborhoods and ZIP codes around South Orange, NJ.

Neighborhoods we cover for backflow testing

  • Village
  • Montrose
  • Seton Hall

ZIP codes we serve

07079

Backflow testing FAQs

Questions about backflow testing

Questions we hear most often about Double Check Valve Testing in South Orange, NJ.

Talk to a person
How often does a backflow preventer need testing in South Orange, NJ?
Most water utilities require a test once a year. Many also require one at installation, after any repair and after the device is moved. Your utility's notice letter gives the exact due date.
Who is allowed to test my backflow device?
A tester who holds a backflow tester certification recognized by your state or your water utility. Many utilities keep an approved tester list and reject reports signed by anyone not on it.
What is the difference between an RPZ and a double check valve?
Both have two independent check valves. An RPZ adds a relief valve between the checks that discharges water to atmosphere if the checks leak, which is why it is required on high-hazard connections.
How much does backflow testing cost in South Orange, NJ?
Pricing depends on device type, size and the local market. Call (833) 990-5874 for current pricing on backflow testing in South Orange, NJ.
Is fire sprinkler backflow testing different?
Yes. Along with the standard check valve test, NFPA 25 calls for an annual forward flow test on fire line backflow assemblies. Results often go to both the water utility and the fire authority.